When Should You Stress a Cable Slab?

Featured Article

The question as to when the proper time to apply the stressing force to the post tensioned cable in this type of reinforced foundation is of considerable interest. If you apply the stressing load too soon you have the danger of pulling cable anchorages out of the green concrete. If you wait too long there is a problem of excessive loads being applied to the foundation, due to the super structure framing proceeding and, probably most significant, the increase in number and width of shrinkage cracks which could occur in the un-reinforced foundation.

Post tensioned slabs should be stressed when the concrete strength designated by the engineer’s plan is reached.  The practice of MLAW has been to apply stress when the concrete reaches 2000 psi. Good quality concrete should reach 2000 psi in approximately 4 days under normal curing conditions, and certainly within 7 days. If 2000 psi is not reached within 7 days, the concrete will probably not reach 3000 psi in 28 days.

Loadings should not be placed on the slab beyond the basic framing and possibly composition shingle roofing. Certainly no sheetrock or any other heavy loads should be applied to the structure before stressing the cables. Remember, the foundation slab is in a totally unreinforced condition prior to stressing.  The best time to apply the stressing would be between 4 and 7 days and certainly before significant loads are applied to the foundation. The strength of the concrete at the time of the stressing should be verified by some type of indirect concrete testing procedure such as an impact hammer or other technique.

Kirby T. Meyer, P.E.
MLAW Consultants & Engineers
Originally published in MLAW Newletter, January 2006

Explore

MLAW Engineers, Structural Engineering, Austin, San Antonio, Houston, Dallas, Temple, Waco, Killeen, Bryan, College Station

Defining Foundation or Structural Failure

By Staff Editor | March 17, 2022

When has a foundation or any other structural unit failed? There are three categories in which a structure could be placed with regard to structural performance: Obvious failure: Collapse Major distress and distortion Functionality Impairment Obvious non-failure: No distress No distortion Not so obvious: Some distress Some distortion Partial functionality impairment Case I and case…

Read More
MLAW Engineers, Structural Engineering, Austin, San Antonio, Houston, Dallas, Temple, Waco, Killeen, Bryan, College Station

Shrinkage Crack Considerations for Post-Tensioned Foundations

By Staff Editor | March 17, 2022

Shrinkage cracks in concrete slab-on-ground foundations are a significant public relations problem to home builders. All concrete will shrink during the curing process which lasts up to a year after the time concrete is placed in the forms. Curing involves loss of water from within the concrete, both when it is in a plastic state…

Read More
Posted in

Staff Editor

MLAW Engineers is recognized as one of the most respected structural engineering firms in Texas. Over 54 years of superior engineering by MLAW Engineers can be seen in over 400,000 completed projects nationwide.

1 Comments

  1. Tino Ambriz on June 13, 2023 at 5:29 pm

    Good afternoon on a 9 inch post tension elevated slab after our stress test is done how long before you take drive any equipment on to continue going up with or put any weight on it

Leave a Comment